Measures for electromagnetic compatibility (EMC)
Installation
5.6.1 Equipotential bonding
For equipotential bonding, the DCS..B option must be connected as follows after it has
been installed in MOVIDRIVE
®
B. Connect the tapped hole [1] with X80:2 of option
DCS..B. For the tapped hole [1], use a grounding screw with tooth lock washer (included
in the delivery) M4 x 8 or M4 x 10 (tightening torque 1.4 - 1.6 Nm).
9007201226141323
X86
MOVIDRIVE
®
MDX61B
BG1 - 7
DCS21B/31B
DCS21B
X80 : 2
[1]
INFORMATION
Proper operation cannot be guaranteed if the DCS..B option is installed in a
MOVIDRIVE
®
B unit without tapped hole. SEW-EURODRIVE recommends to replace
a MOVIDRIVE
®
B unit without tapped hole with a MOVIDRIVE
®
B unit with tapped
hole.