Operating Instructions Chapter 10
Flexi Classic Gateways
8011834/YT28/2016-03-15 © SICK AG • Industrial Safety Systems • Germany • All rights reserved
145
Subject to change without notice
PROFINET IO Gateway
Error type Message
0x910
Configuration/diagnostics error: CRC monitoring module list.
0x911
Configuration/diagnostics error: Monitoring time range constant.
0x912
Configuration/diagnostics error: SALI monitoring event.
0x913
Configuration/diagnostics error: Refer to the user manual for further details on
this error code.
0x914
Configuration/diagnostics error: Flexi Classic extension module has set emergency
bit. Check extension module’s error code for further details.
0x915
Configuration/diagnostics error: Flexi Classic master has set high-emergency bit.
Check master module’s error code for further details.
0x916
Configuration/diagnostics error: Program execution error. Contact SICK service.
0x917
Configuration/diagnostics error: Slot list in extension module is faulty. Contact
SICK service.
0x918
Configuration/diagnostics error: System tick exceeded. Contact SICK service.
0x919
Configuration/diagnostics error: Slot index error. Contact SICK service.
0x91a
Configuration/diagnostics error: Enter key not released while LED was flashing.
Repeat process.
0x91b
Configuration/diagnostics error: Refer to the user manual for further details on
this error code.
0x91c
Configuration/diagnostics error: External error hardware reset. Contact SICK
service.
0x91d
Configuration/diagnostics error: Illegal error opcode reset. Contact SICK service.
0x91e
Configuration/diagnostics error: Error clock generator reset. Contact SICK service.
0x91f
Configuration/diagnostics error: Unexpected reset. Contact SICK service.
0x920
Configuration/diagnostics error: Unknown mask revisions. Contact SICK service.
0x921
Configuration/diagnostics error: Error clock generator loss of lock. Contact SICK
service.
0x922-0x940
Configuration/diagnostics error: Refer to the user manual for further details on
this error code.
0x941
Configuration/diagnostics error: Cross comparison input configuration erroneous.
Contact SICK service.
0x942
Configuration/diagnostics error: Cross comparison output state erroneous.
Contact SICK service.
0x943-0x980
Configuration/diagnostics error: Refer to the user manual for further details on
this error code.
0x981
Configuration/diagnostics error: Too many modules found. Verify that your Flexi
Classic system comprises not more than 12 modules (relay modules excluded).
0x982
Configuration/diagnostics error: Unknown module ID found. Verify that your Flexi
Classic system comprises modules types according to the user manual only.
0x983
Configuration/diagnostics error: Invalid jumper on S1. Check installation.
0x984
Configuration/diagnostics error: Invalid jumper on S2. Check installation.
0x985
Configuration/diagnostics error: Invalid jumper on S3. Check installation.
0x986
Configuration/diagnostics error: Erroneous module configuration. Check program
switch settings, cabling and EDM settings.
0x987
Configuration/diagnostics error: Rotary switch changed during operation. Restore
correct setting and power cycle Flexi Classic system or teach-in new setting.
0x988
Configuration/diagnostics error: Incomplete data frame on IndexAssign. Contact
SICK service.
0x989-0x9ff
Configuration/diagnostics error: Refer to the user manual for further details on
this error code.
0xa01
Logical error: Logical error in input group A.
0xa02
Logical error: Logical error in the start function group A.
0xa03
Logical error: Refer to the user manual for further details on this error code.
0xa04
Logical error: Logical error in the output function group A.
0xa05-0xa07
Logical error: Refer to the user manual for further details on this error code.
0xa08
Logical error: Logical error in the bypass function group A.