Clearing malfunctions
FLOWSIC500 · Operating Instructions · 8025733/1GMJ/V4-2/2022-07 · © SICK Engineering GmbH 103
Subject to change without notice
Table 28 Error messages
Status message Description/clearance
E-3001 The Event logbook is full.
Check the Event logbook. The Event logbook can be reset with the FLOWgate
TM
operating software.
E-3006 Checksum error
p. 102, §6.1 “Contacting Customer Service”.
E-3007 Time invalid
p. 68, §4.2 “Commissioning on the display”.
E-3009 The FLOWSIC500 is in calibration mode.
p. 98, §5.2.9.2, “Starting and terminating calibration mode”.
E-3010 Temperature sensor failure.
The FLOWSIC500 uses the default value specified.
p. 132, §7.6 “Exchanging an external pressure or temperature sensor”
p. 102, §6.1 “Contacting Customer Service”.
E-3012 Pressure sensor failure.
The FLOWSIC500 uses the default value specified.
p. 132, §7.6 “Exchanging an external pressure or temperature sensor”
p. 102, §6.1 “Contacting Customer Service”.
E-3013 Device is outside the permissible measurement pressure range.
Check Pmin/Pmax vs. pressure.
E-3014 Flow rate measurement is in status “Malfunction”,
p. 102, §6.1 “Contacting Customer Service”.
E-3017 The K-factor cannot be calculated.
Check the values entered for gas composition against the reference conditions and
the base conditions.
p. 84, §5.2.4 “Main display (with device option volume conversion)”.
E-3018 Reverse flow
The measured creep volume (reverse flow) is larger than the preconfigured buffer
volume.→ p. 23
If larger reverse flows occur regularly, contact Customer Service to have the
preconfigured volume adapted.
p. 102, §6.1 “Contacting Customer Service”.
E-3019 The measured gas temperature/gas pressure is outside the permissible limits.
E-3019 = Gas temperature is below the alarm limit
E-3020 = Gas temperature is above the alarm limit
E-3021 = Gas pressure is below the alarm limit
E-3022 = Gas pressure is above the alarm limit
Check the set alarm limit values.
p. 92, §5.2.6.7 “Temperature parameters”
E-3020
E-3021
E-3022
E-3023 Time is inaccurate.
Check time synchronisation.