EasyManua.ls Logo

Siemens SIMATIC PCS 7 - Symbolic Names of Inputs and Outputs

Siemens SIMATIC PCS 7
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In terms of hardware requirements, from PCS 7 V8.0 Update 1 you require a CPU with firmware
>= V6.0 and a IM153-4 HF V4.0. For standard CPUs with firmware V5.3, a CP443-1EX30 must
be used as a PROFINET IO controller.
Note
PROFIBUS DP continues to represent the preferred field bus solution for a PCS 7 plant.
Users should use the "SIMATIC Process Control System PCS 7 Engineering System" (https://
support.industry.siemens.com/cs/ww/en/view/109485969) manual for planning PROFINET IO
within PCS 7.
You can find information on configuration and commissioning in the following contributions:
Application example "SIMATIC PCS 7 with PROFINET – Typical Architectures and
Engineering" (https://support.industry.siemens.com/cs/ww/en/view/72887082)
Manual "SIMATIC PROFINET System Description" (https://support.industry.siemens.com/
cs/ww/en/view/19292127)
6.5.3 Symbolic names of inputs and outputs
You can enter symbols directly in HW Config. The screenshot below shows a typical signal list
for a chemical plant, as an example.
Configuration of the hardware (AS and I/O)
6.5 Configuration of the I/O devices
Compendium Part A - Configuration Guidelines (V8.2)
Configuration Manual, 08/2016, A5E38166869-AA 117

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Related product manuals