Internet time
Ensure that the Windows system time is not automatically synchronized via the Internet where
the PC stations are operated in a workgroup (Change date/time > Internet time). This allows
you to avoid corresponding error messages from the Windows time service in the events
display.
Virus scanners
By setting up a virus scan solution you can reduce the risk of plant faults occurring as a result
of malware. Virus scanners approved for PCS 7 can be installed later.
Suitable virus scan software versions from manufacturers "Symantec", "McAfee" and "Trend
Micro" have been tested and approved for each PCS 7 version. You can find the relevant
approved software version in the "PCS 7 Readme" documentation. You will find information
on this in the FAQ "With what are SIMATIC PCS 7 V8.x, V7.x, V 6.x, V5.x, and V4.x
compatible?" (
https://support.industry.siemens.com/cs/ww/en/view/2334224).
Note
Information on installing and managing virus scanners within PCS 7 plants can be found in the
"SIMATIC Process Control System PCS 7 Managing virus scanners (https://
support.industry.siemens.com/cs/ww/en/view/38625951)" document.
Additional software
Only install the software products mentioned in the documentation on a PCS 7 PC, e.g. MS
Office components or burning software. The MS Office applications Word, Excel, and Access
can be used in process mode on client computers (OS, BATCH, Maintenance, WEB).
However, their use may result in significantly reduced performance in some situations. Office
must not be used in process mode on any other operator stations and BATCH stations.
The user bears sole responsibility when third-party products are used. If you require third-party
products, these should be installed before you install PCS 7. PCS 7 and the third-party products
may not run at the same time.
Network security (as part of Lifecycle agreements)
Install a virus scanner solution for the terminal bus and supply this with current patterns.
Only install software approved by Siemens on all stations with process mode.
4.3.4 Installation of PCS 7
Introduction
PCS 7 software is installed automatically via a PCS 7 framework setup. You can find extensive
information on this in the "SIMATIC Process Control System PCS 7 - PC Configuration" manual.
Preparation and administration
4.3 Installation
Compendium Part A - Configuration Guidelines (V8.2)
Configuration Manual, 08/2016, A5E38166869-AA 29

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals