Configuration of the hardware (AS and I/O)
6
Introduction
This section describes the settings in the hardware configuration (HW Config) of the example
project ("Comp_MP").
The screenshots provide an overview of the properties of an H system with CPU 410-5H and
CP 443-1/CP 443-5 Ext as well as of a standard AS with CPU 410--5H and
CP 443-1/CP 443-5 Ext. The properties dialogs of other CPUs or CPs may be slightly different.
Note the following when using SIMATIC PDM in the project:
S7-400 CPUs from firmware version 5.1 and Win AC RTX from software version V4.6 support
data set routing to the internal PROFIBUS DP interface. The CPUs must also be configured
with this firmware version for this purpose. For all other S7-400 CPUs, the required routing
functions must be implemented with a CP 443-5 Ext.
Compendium Part A - Configuration Guidelines (V8.2)
Configuration Manual, 08/2016, A5E38166869-AA 83