PNU (parameter number) and page index
Parameter number PNU Page index
0000 … 1999 0000 … 1999 0 hex
2000 … 3999 0000 … 1999 80 hex
6000 … 7999 0000 … 1999 90 hex
8000 … 9999 0000 … 1999 20 hex
10000 … 11999 0000 … 1999 A0 hex
20000 … 21999 0000 … 1999 50 hex
29000 … 29999 0000 … 1999 70 hex
30000 … 31999 0000 … 1999 F0 hex
60000 … 61999 0000 … 1999 74 hex
Subindex
For indexed parameters, the parameter index is located in subindex as hexadecimal value.
PWE: Parameter value or connector
Parameter values or connectors can be located in the PWE.
Table 8-31 Parameter value or connector
PWE 1 PWE 2
Parameter value Bit 15 … 0 Bit 15 … 8 Bit 7 … 0
0 0 8-bit value
0 16-bit value
32-bit value
Connector Bit 15 … 0 Bit 15 … 10 Bit 9 … 0
Number of the connector 3F hex The index or bit eld
number of the connec‐
tor
Examples
Read request: Read out serial number of the Power Module (p7841[2])
To obtain the value of the indexed parameter p7841, you must ll the telegram of the parameter
channel with the following data:
• PKE, Bit 12 … 15 (AK): = 6 (request parameter value (eld))
• PKE, Bit 0 … 10 (PNU): = 1841 (parameter number without oset)
Parameter number = PNU + oset (page index)
(7841 = 1841 + 6000)
• IND, bit 8 … 15 (subindex): = 2 (index of parameter)
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
200 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL