Default setting 34: Dual Slave mode with setpoint via AS-i 󹪝eld bus
The control accesses the two slaves of the converter each via four bits.
Via slave 2, in accordance with pro󹪝le 7.A.E, the control speci󹪝es the commands listed below (AS-
i.DO0 … AS-i.DO2).
Via slave 1, the control sends the command for quick stop and the data in cyclical or acyclical
mode.
The control requires one bit per slave in order to specify the slave.
Default setting 34, slave 2 with pro󹪝le 7.A.E: Control -> converter
AS-i.DO0 -> ON / OFF 1
AS-i.DO1 -> OFF 2
AS-i.DO2 -> Acknowledge fault
AS-i.DO3 -> Select slave A or slave B, interconnected internally
If the control speci󹪝es the speed setpoint, the converter replies:
Default setting 34, slave 2 with pro󹪝le 7.A.E: Converter -> control
p2080[0] = 53.13 PLC ready to switch on -> AS-i.DI0
p2080[1] = 899.11 Pulses enabled -> AS-i.DI1
p2080[2] = 722.0 State DI0 -> AS-i.DI2
p2080[3] = 722.1 State DI1 -> AS-i.DI3
If the control sends a diagnostic request via AS-i.P0, the converter replies with the currently
pending fault or alarm messages.
AS-i System Interface Manual (https://support.industry.siemens.com/cs/gb/en/view/
1171856).
Default setting 34, slave 1 with pro󹪝le 7.A.5: Control -> converter
AS-i.DO0 -> Time signal for the CTT2 transfer from the AS-i master
AS-i.DO1 -> Data bit for the CTT2 transfer, four bytes cyclically or acyclically via PIV.
The reading and writing of parameters is possible via the PIV. Because
data is transferred bit-by-bit, the read and write process is very slow.
AS-i.DO2 -> p0881 = 2093.4 Override quick stop
AS-i.DO3 -> Select slave A or slave B, interconnected internally
Default setting 34, slave 1 with pro󹪝le 7.A.5: Converter -> control
p2080[4] = 722.2 State DI2 -> AS-i.DI0
p2080[5] = 722.3 State DI3 -> AS-i.DI1
Serial data transfer CTT2, four bytes cyclically or acyclically via PIV. The
reading and writing of parameters is possible via the PIV. Because data
is transferred bit-by-bit, the read and write process is very slow.
-> AS-i.DI2
Time signal for the CTT2 transfer to the AS-i master -> AS-i.DI3
Advanced commissioning
8.7 Control via AS-i
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 211