Warning, Alarm Diagnosis And Counter Measures
V800 Series High Performance Closed-Loop Vector Inverter User Manual
The output current
of U phase is
deficient/smaller
The output current
of V phase is
deficient/smaller
The output current
of W phase is
deficient/smaller
1. The lead from frequency inverter to motor
is disconnected.
2. The driving or control panel of the
frequency inverter is faulty.
3. The three-phase winding of the motor is
faulty.
1. Eliminate peripheral failures.
2. Seek for manufacturer’s support.
3. Eliminate the failure of motor.
The three-phase
input voltage is
unbalanced
(can be shielded)
The imbalance rate of three-phase voltage is
larger.
1. Add AC or DC reactor.
2. Increase the capacity of frequency
inverter.
Program
overcurrent
protection
1:check power grid and working
situation
2:Seek for manufacturer’s support.
AI1 input is
disconnected
A12 input is
disconnected
A13 input is
disconnected
1. The wiring of input analog signal is
disconnected or analog input signal
source is inexistent.
2. Parameters related to disconnection
detection are configured improperly.
1. Inspect the wiring of analog input
signal and the analog input signal
source.
2. Modify the configuration
parameters.
1. The wiring of pulse input signal is
disconnected or analog input signal
source is inexistent.
2. Parameters related to disconnection
detection are configured improperly.
1. Inspect the wiring of pulse input
signal and analog input signal
source.
2. Modify the configuration
parameters.
The rotating speed
detection loop is
disconnected
1. The speed measuring module is
incorrectly connected.
2. The wiring of speed measuring module is
disconnected.
3. The output of speed measuring module is
abnormal.
4. Relevant function codes are set
improperly.
1. Inspect the connection of speed
measuring module.
2. Modify the parameter setting.
3. Seek for manufacturer’s support.
The motor fails to
be connected when
the motor
parameters are
identified.
The motor fails to be connected when the
motor parameters are identified.
U phase output is
disconnected or the
parameters are
seriously
unbalanced
1. The lead from frequency inverter to motor
is disconnected.
2. The driving or control panel of the
frequency inverter is faulty.
3. The three-phase winding of the motor is
faulty.
1. Eliminate peripheral failures.
2. Seek for manufacturer’s support.
3. Eliminate the failure of motor.
V phase output is
disconnected or the
parameters are
seriously
unbalanced
1. The lead from frequency inverter to motor
is disconnected.
2. The driving or control panel of the
frequency inverter is faulty.
3. The three-phase winding of the motor is
1. Eliminate peripheral failures.
2. Seek for manufacturer’s support.