EMC 231
V800 Series High Performance Closed-Loop Vector Inverter User Manual
◆ Type and length of motor cable
6) When leakage current of inverter cause leakage circuit breaker work:
◆ Improve sensitivity of the current value of leakage circuit breaker
◆ Replace a new leakage circuit breaker with high frequency inhibition function
◆ Reduce carrier frequency
◆ Shorten length of output cable
◆ Install a leakage suppression equipment
12.8 COMMON EMC INTERFERENCE PROBLEM AND SOLUTION
Frequency inverter is strong anti-interference equipment, when there is problem in
wiring and ground connection, still maybe will comes out interference. When it happens,
Leakage protection
switch trip
◆ Motor case connect the PE of frequency inverter;
◆ Frequency inverter PE connect the power system PE;
◆ Add Safety capacitance box on input power wire;
◆ Add magnetic loops on input power wire;
Running Drive leads
Interference
◆Motor case connect the PE of frequency inverter;;
◆Frequency inverter PE connect the power system PE;
◆Add Safety capacitance box and magnetic loops on input power
wire;
◆ Add Capacitor or magnetic loops on the interferenced port ;
◆ Share the ground wire between the equipments;
Communication
Interference
◆Motor case connect the PE of frequency inverter;;
◆Frequency inverter PE connect the power system PE;
◆Add Safety capacitance box and magnetic loops on input power
wire;
◆Add matched resistor On communication wire and load end;
◆ Add communication common GND on communication wire;
◆communication wire use shielded wire, shields connect public
Communication;
◆ Add capacitor filter on low-speed DI, maximum 0.1uF;
◆Add capacitor filter on AI, maximum 0.22uF;
◆Analog signal use shielded wire, shields connect PE of frequency
inverter.
Remark:If you have any other EMC interference questions, please contact the