Functional Parameter Table
V800 Series High Performance Closed-Loop Vector Inverter User Manual
Setting Range and Description
1: Trip out when phase sequence goes wrong
2: The warning of no shutdown when phase
sequence goes wrong
6.2.48 CORRECTION PARAMETER
Setting Range and
Description
AI1 zero offset adjustment
4mA offset adjudgements for AI2
AI3 zero offset adjustment
AO1 zero offset correction
AO2 zero offset correction
under voltage action level
Correction coefficient of DC side
voltage detection value
6.2.49 SPECIAL FUNCTIONAL PARAMETERS
Setting Range and Description
Torque limit configuration
(H)
_ _ _ X: Constant torque area torque
limitation
0: Only limited by torque limiting
parameter (including Revolution PID
output limit)
1: Also limited by acceleration and
deceleration current level and
maximum permitted current
_ _ X _: Reserved
_ X _ _: Constant power area torque
limitation
0: Treated the same as the constant
torque area
1: Simultaneously adjusted as per
constant power algorithm
Current closed-loop
proportional gain
Current closed-loop
integration time constant
Total leakage inductance
compensation constant