Functional Parameter Table
V800 Series High Performance Closed-Loop Vector Inverter User Manual
66
Function
Code
Name
Setting Range and Description
Minimum
Unit
Factory
Default
Change
Limit
F6.1.35
Stage 5 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.36
Stage 6 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.37
Stage 7 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.38
Stage 8 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.39
Stage 9 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.40
Stage 10 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.41
Stage 11 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.42
Stage 12 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.43
Stage 13 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.44
Stage 14 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
F6.1.45
Stage 15 running time
0.0~6500.0(Sec./Min.)
0.1
0.0
6.2.30 SWING FREQUENCY OPERATION
Function
Code
Name
Setting Range and Description
Minimum
Unit
Factory
Default
Change
Limit
F6.2.46
Function selection
(H)
_ _ _ X: Function Setting
0: Function closed
1: Function effective
2: Terminal selectivity effective (Function
No.24)
_ _ X _: Stop restart mode
0: Start with the memory status before stop
1: Restart
_ X _ _: Swing control
0: Fixed swing (relative maximum frequency)
1: Variable swing (relative central frequency)
X _ _ _: Status storage
0: Not saved after power-off, and run again
after restart
1: Save the status after power-off,and run
again from the saved status
1
0000
×
F6.2.47
Swing frequency
preset frequency
0.0~[F0.1.21]
0.01
10.00
F6.2.48
Preset frequency
waiting time
0.0~6000.0Sec.
0.1
0.0
F6.2.49
Swing frequency
amplitude
0.0~50.0(%)
0.1
10.0
F6.2.50
Sudden jump
frequency
0.0~50.0(%)
0.1
10.0
F6.2.51
Triangular wave
rising time
0.1~1000.0Sec.
0.1
10.0
F6.2.52
Triangular wave
decreasing time
0.1~1000.0Sec.
0.1
10.0
F6.2.53
Frequency setting
in the center of the
swing frequency
0.0~[F0.1.21]
0.01
10.00