Vertiv | Liebert® STS2/PDU
User Manual | Rev. 6 | 10/2017 69
8.1.2 Reliability and Agency Requirements
The Liebert STS2/PDU is designed for high reliability and high availability with a critical bus Mean Time Between
Failure (MTBF) exceeding 1,000,000 hours.
The Liebert STS2/PDU and all its options are designed, tested and certified, where applicable, to meet agency
requirements as follows:
UL 891: Standard for Switchboard, for UL and ULc listing
UL 1008: Standard for Automatic Transfer Switches
UL 67: Standard for Panelboard
UL 1561: Standard for Dry Transformers
UL 1459: Telephone equipment (Modem)
•NEC
FCC Part 15 EMI emission limits for Class A computing devices.
•U.S. Department of Energy 2016
The Liebert STS2/PDU uses conservatively rated components, minimizing the need to go to maintenance
bypass. All normal maintenance and repair work can be done through the front panel of the unit. This access
makes repairs and maintenance easier.
Gating and control logic are partitioned so that failure of one source’s gating or sensing logic does not prevent
the switch from transferring to the other source.
All control and logic components are mounted separate from the power components. The Liebert STS2/PDU is
designed to minimize the exposure of hazardous voltages to allow safe servicing of the unit while the load is
energized.
All electrical components requiring normal maintenance are replaceable without de-energizing the load, as long
as one source is available. Solid-state switching devices are packaged to allow safe repair of those devices
without having to de-energize the load. All non-automatic switches or circuit breakers are the plug-in or draw-
out type to allow replacement without de-energizing the load. All other components, including transformers,
power cables and connections, circuit breaker bases, etc., are replaceable from the front, rear or top of the unit
however, this requires all power to be removed from the unit for safety. All solid-state power switching devices
are rated to prevent hazardous device failure in power systems with available fault currents up to the defined
limits, as listed in 14.1.6 - Electrical Requirements.
8.1.3 Factory Backup and Service Assistance
Because improper installation can cause a system to fail, a Vertiv Services or a factory-trained service technician
should thoroughly inspect the unit to ensure it is properly installed and its operating parameters are properly
configured.
Once the Liebert STS2/PDU is properly installed, you, as the on-site operator, can easily monitor the unit’s
operation utilizing the touchscreen.
In the United States, if you need assistance or have questions, call 1-800-LIEBERT (1-800-543-2378).
Outside the 48 contiguous United States, contact Vertiv Services, if available in your area.
For international areas not covered by Vertiv Services, the Vertiv-authorized distributor can provide technical
support.
8.2 Modes of Operation
8.2.1 Normal (Preferred Source)
Under normal operating conditions, the Liebert STS2/PDU routes power from the preferred input source to the
output load. The unit monitors the voltage, current and phase of each source to ensure that both are operating
within set tolerances and that the alternate source is available, should a transfer be required.