User Manual | Rev. 6 | 10/2017 6
2.4 Altitude
The standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See Figure 1 for
recommended deratings for altitudes greater than 4000 feet (1200m).
Figure 1 Recommended derating for high altitude operation
Operation at full load at a higher altitude can be accommodated in ambient temperatures less than 104°F (40°C)
ambient. Figure 2 shows the maximum allowable ambient temperature for full load operation at altitudes above
4000 feet (1200m).
Figure 2 Maximum ambient temperature for full load operation at higher altitudes