Configuration
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 144
Control equipment
i
Note
Control equipment cannot yet be linked with software version 3.5.2. It will be included in a future
software version.
All linked control equipment located in a room, group or zone on the original control device is displayed and used
on the linked control device as aggregated control equipment. The individual events cannot be differentiated. A
key pressed on control equipment in one location is interpreted as a key pressed on all control equipment in every
location. The aggregated control equipment is marked with the following icon:
The following events in a room, group or zone are transferred from the original control device (generator) to the
linked control device (consumer):
· Scene recall and dimming/brightening via control equipment
· Scene recall via the LITECOM web application (e.g. via a touch panel)
· Scene recall via BACnet
The control equipment adopts the configuration of the original control device. This configuration cannot be
changed on the linked control device.