Configuration
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 150
10.12 DALI data
The LITECOM system allows you to poll DALI data on devices. You can use the DALI data profile to define the
properties that are polled. There are static and dynamic properties.
· Static properties are automatically polled during addressing and when a device is being replaced. Static
property polling cannot be disabled in the DALI data profile.
· Dynamic properties change over the course of time and are periodically polled. Dynamic property polling can be
enabled or disabled for each property in the DALI data profile. The frequency of polling (low, medium, high) can
also be defined. If energy data polling is enabled in the settings, Energy is displayed under “Frequency”. A
property is polled at a defined interval depending on the set frequency.
Frequency
Interval
Limit
Low
12 h
No limit
Medium
4 h
Max. 100 properties
High
15 min
Max. 10 properties
Energy
15 min
-
i
Note
After the function is enabled, the DALI data can be accessed via the REST API & MQTT.
For more information see REST API & MQTT manual