Configuration
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 74
Parameter
Description
Test group
(Only for self-contained emergency luminaires)
During a duration test, a power failure is simulated in order to test whether
the emergency luminaire is functioning properly and whether the battery
achieves its nominal operating duration. In order to ensure that a previous
duration test has not emptied all batteries in an emergency, a duration test
is not performed simultaneously for all self-contained emergency
luminaires; the emergency luminaires are tested in two test groups (test
group A and test group B). A test group is a group of self-contained
emergency luminaires that are tested simultaneously during an automatic
duration test.
The self-contained emergency luminaires are automatically assigned to test
groups A and B during addressing. The assignment takes place alternately.
The assignment can be changed at any time.
WARNING
If test groups are incorrectly assigned, the emergency
lighting will not function.
If too many emergency luminaires are tested simultaneously,
the emergency lighting function cannot be guaranteed in an
emergency.
· Ensure that the emergency luminaires are distributed
equally between test group A and B, e.g. 25 emergency
luminaires in test group A and 25 emergency luminaires in
test group B.
· Ensure that all emergency luminaires in the test groups are
also spatially distributed.
Info text 13
(Only for self-contained emergency luminaires)
Information entered by the user for the self-contained emergency luminaire
(e.g. lamp type, article number).
Table 23: Configuration options – Luminaires
10.3.2 Configuration options: motors
Path: App overview > System image
Motors for the following building services can be installed in your LITECOM system:
· Blinds
· Screens
· Window
i
Note
The default configuration of these devices can only be changed using the Mobile Maintenance Tool
commissioning software from Zumtobel.