Commissioning
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 42
Note
The sky scanner and weather station are automatically added to the system image after the
LITECOM CCD is restarted. They therefore do not need to be addressed.
General procedure for addressing in the LITECOM web application
1. Select device category to be addressed (e.g. luminaires).
2. The location method must also be selected for input devices: Select actively (Physical Selection method) or
Search via interface (locate).
3. Locate the device in the field.
More information can be found here...
Locate the device visually in the field.
Note
Visual location: a location method in which a network or bus subscriber can be found visually using
its address in the field.
Example:
· Emergency luminaire indicates its address as a binary flashing pattern using the status LED.
4. A type is assigned to the device.
The type is automatically selected, if possible.
More information can be found here...
5. Assign a room and a group to the device.
6. Optionally, change the device name.
Note
· We recommend using the addressing wizard to address the devices.
For more information see Section Addressing wizard
· Every time there is a change on a DALI control line or on the LM-Bus the affected LITECOM CCD
control device must be restarted in order for the changed field to be imported correctly.