Configuration
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 63
Service
Port
Proto-
col
Comm.
service
In-
coming
Out-
going
Client
Server
Description
LITECOM infinity
45111
UDP
Multi-
cast
x
x
Control device
Control
device
OM multicast
(data interface)
Multicast via IPv4:
239.1.1.1
Port and IP address
can be configured
45112
UDP
Multi-
cast
x
x
CMD multicast
(command interface)
Multicast via IPv4:
239.1.1.2
Port and IP address
can be configured
2222
TCP
HTTP
x
x
User management
Infinity system
4444
TCP
HTTP
x
x
User management
Infinity system
NTP
123
UDP
NTP
x
Control device
NTP
server
Time synchronisation
LITECOM Mobile
App, LITECOM-
Touchpanel TCI,
emLINK v3
443
TCP
HTTPS
x
LITECOM Mobile
App, LITECOM-
Touchpanel TCI,
emLINK
Control
device
HTTPS web
application
8889
TCP
HTTPS
x
WSS WebSocket
Secure
4445
TCP
HTTPS
x
HTTPS user
management
Network
location
5353
UDP
mDNS
x
LITECOM Mobile
App, LITECOM-
Touchpanel TCI,
emLINK
Control
device
Automatic control
device search by
LITECOM Mobile App,
LITECOM-Touchpanel
TCI, emLINK
Multicast via
IPv4: 224.0.0.251
or IPv6: ff02::fb
SSH
22
TCP
SSH
x
SSH client
Control
device
Direct connection
to control device;
access for
development
Service
interface
6852/
6853
TCP
x
Gateway client
(service
interface)
Control
device
Direct connection
to service interface
via analysis tools like
MMT
and LMW-ADMP
Only available if a
connection to the
service interface
is permitted.
Table 22: Network ports used
i
Note
The following ports are no longer used in software version 3.5.0 and higher: 2222, 4444, 4445, 8887,
8889