Configuration
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 76
Parameter
Description
i
Note
If a conventional presence detector is connected to a
standard switch input device(e.g. ED-SxED, LM-SxED),
the Std switch operating mode must be selected. A
conventional presence detector does not send any
information directly to the bus; the presence information
is only forwarded electrically using the contact state.
Presence scene*
Scene, which the user recalls using the momentary-action
switch/standard switch when entering the room.
Absence scene*
Scene, which the user recalls using the momentary-action
switch/standard switch when exiting the room.
Fade time to presence scene*
Time during which the absence scene changes to a value (scene,
presence value).
Fade time to absence scene*
The time it takes to change from one value (scene, presence value)
to the absence scene.
Mode of operation (presence/absence scene)*
Mode of operation controlled when the presence or absence scene
is recalled.
Mode of operation (dim/brighten)*
Mode of operation controlled during dimming/brightening.
i
Note
Mode of operation Tunable White is only supported by
TW luminaires (DALI Device Type 8). The colour
temperature of TW luminaires (special luminaires)
cannot be changed via momentary-action
switch/standard switch.
Table 24: Configuration options – Momentary-action switch/standard switch
i
Note
Whether parameters marked with an asterisk (*) can be configured depends on the selected
operating mode. The following table provides an overview of which parameters can be configured in
which operating mode.