The contacts of the switch or relay must open/close within 200 ms of each other.
Cable types and lengths
Double-shielded twisted-pair cable is recommended.
Maximum cable lengths:
Frames R0…R2: 100 m (330 ft) between activation switch [K] and drive control
board
-
- Frames R3…R8: 300 m (1000 ft) between activation switch [K] and drive control
board
60 m (200 ft) between external power supply and control board
Note:
A short-circuit in the wiring between the switch and an STO terminal causes a dangerous
fault. Therefore, it is recommended to use a safety relay (including wiring diagnostics) or a
wiring method (shield grounding, channel separation) which reduces or eliminates the risk
caused by the short-circuit.
Note:
The voltage at the STO input terminals of the drive must be at least 13 V DC to be interpreted
as “1”.
The pulse tolerance of the input channels is 1 ms.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control board at
the control board only.
Ground the shield in the cabling between two control boards at one control board only.
The Safe torque off function 153