Chapter 4 – Configuration
12 TRAVELING WAVES RECORDER
The RPV311 allows user to configure a traveling wave recorder for fault location, by trigger. To start the
configuration, it is necessary add a new recorder in accordance with the position of selected links in
equipment.
Once created, the traveling wave recorder can be configured as per the section shown in Figure 35.
Figure 35: Traveling waves recorder – trigger’d recording configuration section
A The ENABLED check box allows user to enable the fault recorder feature.
B The TERMINAL text field allows user to enter the terminal of this recorder.
C The TRIGGER LOGIC field contains all the thresholds created. The logic equation uses AND and OR logic
operators over previously defined thresholds. Initially, all preset thresholds are displayed as implicit OR
operators, one per line.
To enable thresholds individually, click on the threshold and select Enable;
To disable discarded thresholds individually, click on the threshold and select Disable;
To break or remove complex thresholds, click on the threshold and select Cut last;
To create equations with AND operators, follow the procedures below:
o Click on the threshold and select Cut last;