Chapter 4 – Configuration
11 DISTURBANCE RECORDER
The RPV311 allows user to configure triggered and continuous disturbance recording.
11.1 TRIGGER'D RECORDING
In this section, shown in Figure 33, it is possible to configure the equipment disturbance triggered recorder.
Figure 33: Disturbance recorder – trigger’d recording configuration
A The ENABLED check box allows user to enable the disturbance triggered recorder feature.
B The PRE TIME text field allows user to enter the recording time before the event in seconds. The POST TIME
text field allows user to enter the recording time after the event in seconds. The TIME OUT text field allows
user to enter the maximum times in seconds, where the event will be recorded. The DISABLED FOR – MINUTES
IF MORE THAN – TRIGGERS IN THE LAST – SECONDS allows user to disable recorder if the event repeats within a
programmed time period.
C The TRIGGER LOGIC field contains all the thresholds created. The logic equation uses AND and OR logic
operators over previously defined thresholds. Initially, all preset thresholds are displayed as implicit OR
operators, one per line.