Chapter 16 Maintenance and Troubleshooting
RPV311
RPV311-TM-EN-6
305
4 RPV311 FIRMWARE UPDATE
When installing the application software package accompanying the equipment (refer to Software
Installation), the Firmware Upgrade Tool (FUT) is installed and associated having an files with extension .fw
allowing an RPV firmware update to be easily carried out by user.
The steps to be followed for updating the equipment firmware are:
1. Request Alstom for the firmware file.
2. Copy the file to the PC on which the RPV application software is installed (see Software Installation).
The file shall have a .fw extension.
3. Double click file.
4. A screen opens and if it is the first time connection between the local PC and the equipment is made
an acknowledgement message will appear in the interface. Answer Y and press ENTER;
5. Provide the RPV IP address in the 192.168.0.160 format and press ENTER;
6. Enter the password for firmware updating and press ENTER;
7. The entire updating process is performed automatically and can be followed on the PC screen;
8. The process requires resetting of the equipment. Therefore, answer Y. Equipment will take a few
minutes to return to normal operation;
9. After performing the update operation, press ENTER to end.
The updating operation log can be checked locally in the fut.log file which is in the folder where the RPV
software has been installed.