Chapter 13 RPV Manager
RPV311
RPV311-TM-EN-6
239
Figure 91: Terminal name configuration
8. Finally, enter the name of the transmission line.
Contacts
This menu configures the contacts to which the RPV can send emails notifications.
On this window the user can view the list of registered contacts, add, edit, or remove any contact. During the
removal of any contact, if any association with any warning, a confirmation message will be displayed to the
user.
Warnings
On this screen the user can view the list of warnings, add, edit or remove any warning.
By setting the warning the user can select which contact will receive the alarms.
You can also inform you which types of alarms to be sent:
equipment alarm,
line fault information,
voltage channel
When the option Attach COMTRADE is selected, the software will send the selected the zic file
corresponding to the "line fault information and/or voltage channel" to the contact.
Line fault information: when possible the software will send the saved fault data within two days
and will also send the corresponding COMTRADE.
Voltage channel: when there is a record that exceed 20% RMS voltage the software sends the
email with relevant information and also sends the COMTRADE.
3.2.3 POLLING MENU
In the Polling menu, the user can:
Select software polling to be manual;
Select software polling to be automatic;
In the manual mode, both the Refresh of the COMTRADE list and the download of register has to be
commanded by the user.