Chapter 9 MODBUS
RPV311
192
RPV311-TM-EN-6
2.3 ANALOG DATA
The user must manually associate analog data to a register number. The following analog data can be
selected:
RMS value of voltage and current circuits (any phase);
Voltage and current synchrophasors (any phase, angles are sent in degrees units);
Frequency of voltage and current circuits;
Positive sequence of voltage and current circuits;
Negative sequence of voltage and current circuits;
Imbalance of voltage and current circuits;
Total harmonic distortion of voltage and current circuits;
Apparent combined power of power circuits;
Apparent fundamental power of power circuits;
Active fundamental power of power circuits;
Reactive fundamental power of power circuits;
RMS value of transducer channels.
2.4 DIGITAL CHANNELS
All digital channels are reported in groups of 8 channels. A register data is composed of 16-bit data where
the least significant bit represents the state of the first digital channel of the group. The user must manually
associate a digital group with a register number.
2.5 CONFIGURATION
The MODBUS configuration is carried out through the Web Interface. For details about the MODBUS
configuration see Chapter 4.

Table of Contents