Chapter 15 – Installation
Figure 118: Screws of the Back Panel
Remove the board corresponding to the channel to be configured. For each channel to be configured for
current, connect the jumper between positions 2 and 3 as shown in Figure 119.
Figure 119: Internal Jumper
Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring terminal, and M3 holes.