Figure 93: Polling configuration
Polling Configuration fields description:
COMTRADE Directory: directory path where the new records are downloaded and where the fault locator
calculation searches.
Display Downloaded COMTRADES Limit: maximum COMTRADE records already downloaded that will be
displayed on the screen
Display Available COMTRADE Age (day): limit, in days, of downloaded records that will be fetched and
displayed on the screen.
COMTRADE DAT File: format in which the COMTRADE file will be saved.
Check Voltage Channel > 20% RMS: checks to see if there is a deviation greater than 20% in the value of
the RMS nominal voltage.
Start Auto Polling on Init: starts Auto Polling automatically by the application.
Automatic Fault Location: performs the fault location calculation after the COMTRADE file refresh.
Auto Refresh Interval (min): interval, in minutes, that anautomatic update of the data of the device will run
when the Auto Polling is active.
Auto COMTRADE Polling Interval (min): interval, in minutes, that will be held the automatic download of
COMTRADE files.
Auto Polling COMTRADE Age (day): maximum age, in days, of records that will be downloaded
automatically in Auto Polling. For example, if a register was made 5 days ago and the RPV Manager is
started today and the Auto Polling COMTRADE Age (day) is set to 4 (or 1, 2 or 3) the register will not be
downloaded during the auto polling.
Equipment Request Limit: limit of records that will be requested from the equipment in each query.
Retrieve Fault: When selected, automatically downloads the short duration records, both triggered and
continuous.