3.3 STATUS
In the Status screen the statuses of the equipment and of the links are shown.
If any information of the Status screen indicates a parameter different of the normal operation of equipment,
such indication will be shown in red.
3.3.1 EQUIPMENT STATUS
The Equipment screen, shown in Figure 55, displays a summary of the status of the equipment.
Figure 55: Equipment status screen
A Equipment status, with the following information:
Date: indicates the date the equipment status was last updated in the yyyy-mm-dd hh:mm:ss + 0000
format where o is UTC time offset;
Equipment: indicates whether the equipment is operational or not;
Synchronization: indicates locked if receiving a valid IRIG-B signal and the acquisition system is
synchronized with the IRIG-B signal, even if the time quality is different of locked;
Time quality: indicates the received IRIG-B signal quality;