Chapter 17 Technical Specifications
RPV311
RPV311-TM-EN-6
325
RA33x Environmental Conditions
Operating temperature range
-40 … +55 °C
Maximum operating altitude
2000 m (6560 ft)
Relative humidity
5 … 95 % noncondensing
Tested as per 60068-2-1
-40°C
Tested as per 60068-2-2
+85°C
3.11 TYPE TESTS RA33X
EMC tests were performed according to IEC 60255-26 referring to the following standards
Type Tests RA33x
IEC 61000-4-2:2008
8kV contact / 15KV air (level 4)
IEC 61000-4-3:2006
10 V/m
IEC 61000-4-4:2012
2 KV @ 5KHz (level 3)
IEC 61000-4-5:2005
Differential mode: 1KV
Common mode: 2KV
(level 3)
IEC 61000-4-6:2008
10V
IEC 61000-4-8:2009
30A/m continuos - 300A/m @ 1s.
IEC 61000-4-11:2004
IEC 61000-4-29:2000
A.C. and d.c. voltage dips
Test level: 0% residual voltage
Duration time
a.c.: 1 cycle
d.c.: 16,6ms
Test level: 40% residual voltage
Duration time
a.c.: 12 cycles