EasyManua.ls Logo

Alstom Reason RPV311 - Page 326

Alstom Reason RPV311
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RPV311
Chapter 17 Technical Specifications
RPV311-TM-EN-6
326
d.c.: 200ms
Test level: 70% residual voltage
Duration time
a.c.: 30 cycles
d.c.:500ms
A.C. and d.c. voltage interruptions
Test level: 0% residual voltage
Duration time
a.c.: 300 cycles
d.c.: 5s
IEC 61000-4-17:1999
Test level: 15 % of rated d.c. value
Test frequency: 120Hz, sinusoidal waveform.
IEC 61000-4-18:2006
Voltage oscillation frequency: 1MHz
Differential mode: 1kV peak voltage;
Common mode 2,5kV peak voltage
Gradual Startup
Shut-down ramp: 60s
Power off: 5m
Start-up ramp: 60s
CISPR11:2009
Radiated emission
Limits:
30 to 230MHz - 50dB(μV/m) quasi peak at 3m
230 to 1000MHz - 57dB(μV/m) quasi peak at 3m
CISPR22:2008
Radiated emission
The definition of the limit frequency is based on the maximum internal
frequency of the equipment. On RA33x, the maximum internal
frequency is 100 MHz. For this case, the levels of CISPR 11 satisfy the
normative IEC 60255-26.
Conducted emission

Table of Contents