Chapter 17 – Technical Specifications
d.c.: 200ms
Test level: 70% residual voltage
Duration time
a.c.: 30 cycles
d.c.:500ms
A.C. and d.c. voltage interruptions
Test level: 0% residual voltage
Duration time
a.c.: 300 cycles
d.c.: 5s
Test level: 15 % of rated d.c. value
Test frequency: 120Hz, sinusoidal waveform.
Voltage oscillation frequency: 1MHz
Differential mode: 1kV peak voltage;
Common mode 2,5kV peak voltage
Shut-down ramp: 60s
Power off: 5m
Start-up ramp: 60s
Radiated emission
Limits:
30 to 230MHz - 50dB(μV/m) quasi peak at 3m
230 to 1000MHz - 57dB(μV/m) quasi peak at 3m
Radiated emission
The definition of the limit frequency is based on the maximum internal
frequency of the equipment. On RA33x, the maximum internal
frequency is 100 MHz. For this case, the levels of CISPR 11 satisfy the
normative IEC 60255-26.
Conducted emission