Chapter 4 – Configuration
The RPV311 processing module can be configured with up to 8 Subscription links.
To configure the links, access the SAMPLED VALUES SUBSCRIPTIONS section, shown in Figure 14.
Figure 14: Sampled Values subscriptions links configuration section
A The ENABLED check box allows user to enable the Subscription link feature.
B The SAMPLED VALUE IDENTIFIER text field allow user to insert the monitored Sampled Values identification.
C The MAC ADDRESS text field allow user to insert the monitored Merging Unit MAC Address.
D The APP ID text field allow user to insert the monitored Sampled Values APP ID.
E The VLAN ID text field allow user to insert the VLAN ID of the monitored Sampled Values.
F The VLAN PRIORITY scroll box allow user to select the priority of the Sampled Values data at the configured
VLAN.
G The SAMPLE RATE scroll box allow user to select the Sampled Values sample rate. 80 points-per-cycle is
used for protection purposes and 256 points-per-cycles is used for measurement purposes.
H The PACKET LOSS TOLERANCE allow user to insert a package-loss rule.
In the Inputs section, shown in Figure 15, it is possible to configure the analog inputs of the Sampled Values
configured in the previous section. It is important to configure the analog inputs for voltage or current,
according to the Sampled Values messages received of the monitored Merging Unit.