Chapter 6 Records
RPV311
160
RPV311-TM-EN-6
There is an user-configurable trigger burst limiter for the fault recorder.
The burst limiter is based on the number of triggers time interval (both parameters are user-configurable).
When the limit is exceeded, recording will be disabled for a period of time defined by the user.
Parameter
Allowed values
Increment
Number of triggers
0 … 12
1
Time interval
0 … 60 s
1 s
Disabling time
1 … 60 min
1 min