Power line file configuration
Nominal length of the line as the owner of the
line claims (in kilometers)
Is the coefficient related to the length of the
line, represents the actual length of the cable of
the line.
This value can be adjusted using data of faults
subsequent to the commissioning
Is the coefficient related to the light speed
factor
<terminal_a>Location,Identifier,Line</terminal_a>
STATIONID,DEVICEID and the terminal
identifier
<terminal_b>Location,Identifier,Line</terminal_b>
STATIONID,DEVICEID and the terminal
identifier
<tower id=”X” name=”NAME”>
Is the identification of the towers and their
geographic coordinates. This information must
be provided by the user
<longitude>nnn</longitude>
The geographic coordinates are optional and must be provided by the user.
The technical note "Traveling Wave Fault Locator (NT0802)" shows how the coefficients K1 and K2 are
calculated.
A model of the power line configuration file is created in the directory C:RPVfaultlocatorconf of Windows
after the RPV Tools installation. The power line configuration model is shown below.
?xml version="1.0" encoding="UTF-8"?
line
length100/length
k1100k1
k21k2
terminal aLOCATION,IDENTIFIER,LINEterminal a