Chapter 13 RPV Manager
RPV311
RPV311-TM-EN-6
247
2. To set the update interval change the field "Auto Refresh Interval " on the Configuration>Polling
menu;
3. To activate or deactivate the Auto Refresh, access the Polling menu and choose between Manual or
Auto options;
4. To ensure that the software starts with the Auto Refresh option active, check the box "Auto Polling
on Init" on the Configuration>Polling menu;
The refresh action also happens during the:
Start of application execution;
Change in list of substations;
Change in the equipment list.
After communication with the equipment, the software checks if any information was changed and updates
the information as follows:
Interface: System Monitor equipment tree tab and equipment lists in the other tabs;
Database;
Information of the Transmission Line configurations for each device;
Name of the directory where the new records will be downloaded.
3.4.2 POLLING
The polling routine is responsible for performing the automatic download of records from each equipment.
Configure the Auto Polling as follows:
1. For each equipment if you want to have Auto Polling functionality, "Enable Auto COMTRADE
Download " should be enabled.
2. To set the update interval, the field "Auto Polling Interval" must be changed in the Polling
configuration screen.
3. To activate or deactivate the Auto Polling, access the menu Polling Auto, to activate, and Polling >
Manual, to disable.
4. To ensure that the software starts with the Auto option active Polling, select the field "Auto Polling on
Init" on the Polling configuration screen
5. COMTRADES records will only be downloaded that are younger than the period entered in the field
“Polling COMTRADE Acts ", in Polling configuration screen,
6. Only the types of COMTRADE records configured through the fields "Retrieve ..." in the Polling
configuration screen of will be downloaded.
7. To run the fault location algorithm automatically after downloading a COMTRADE record, select the
field "Automatic Fault Location", in Polling configuration screen.
8. Once everything is configured, the records will be downloaded to the directory "COMTRADE
Directory "/Records.