Power supply voltage
(AC, phase to phase voltage)
[V]
235
470
705
940
1175
1410
1645
1880
2015
2350
Total additional capacitance connected to
the DC link [µF]
Example:
connected to the DC link
1
2
3
4
5
6
7
8
9
10
No. of additional devices
Installation
Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11
117
of 218
7
Installation notes
Figure 50: Max. external capacitance that can be connected dependent on the power supply voltage
F1 Fuses (cable protection+ device protection)
F10-F15 Option: a destruction of the next device can be avoided
F4 Fuse for the 24 V-voltage supply
Filter The supplying device must be connected to a filter
CAUTION!
The maximum number of devices or the maximum DC link capacitance that can be
connected depend on the power supply voltage, see ZFigure 50– on page 117.
The required waiting time between two charging procedures depends on the external
connected DC link capacitance, see ZFigure 51– on page 118