Maintenance
Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11
169
of 218
9
m Solenoid switch and relays in the main circuit
Check points Methods and criteria Inspection intervals
Daily Semi-
a
nnu-
ally
Annu-
ally
Are there any loose screws? Visual and audio check Tighten screws, if necessary. O
Do the switches function correctly? Visual inspection O
m Plug connectors in the main circuit
Check points Methods and criteria Inspection intervals
Daily Semi-
an
nu-
ally
Annu-
ally
Are there any loose screws or connectors? Tighten screws and firmly stick in plug connector. O
Are there any noticeable odors or color
changes?
Visual inspection and odor check O
Is there any cracking, damage, deformation or
c
orrosion?
Visual inspection O
Is there any leaking fluid or deformation of the
cap
acitors?
Visual inspection O
m Cooling system fans
Check points Methods and criteria Inspection intervals
Daily Semi-
an
nu-
ally
Annu-
ally
Are there any abnormal noises or vibrations? Visual and audio check O
Are there any loose screws? Tighten the screws. O
m Cooling system ventilation duct
Check points Methods and criteria Inspection intervals
Daily Semi-
an
nu-
ally
Annu-
ally
Are there any obstructions in the h
eat sink, air
supply or air outlet?
Visual inspection O