SENSseries LB 480 Level measurement
BERTHOLD TECHNOLOGIES GmbH & Co. KG
3 – 385
Volume 3 Menu Structure
3
2 Operating Mode Displays the operating status of the measurement. One of the fol-
lowing status messages is displayed:
RUN
The measurement is in the normal measurement mode.
WARNING
A warning is displayed and the following steps are carried out:
entry in the error log (the error is stored in the error mem-
ory)
the error will be reported digitally via HART
®
the error is reported binary via the digital output (Digital
Out) if this output has been set to WARNING + ERROR
(see chapter 2.30, page 3-357)
If the error is no longer displayed in Active Error, you can
check the error log (Device Config Diagnostic Log,
page 3-387). In chapter 8 on page 3-429 you find a list of pos-
sible causes and troubleshooting procedures.
ERROR
An error is displayed and the following steps are carried out:
entry in the error log (the error is stored in the error mem-
ory)
the error will be reported digitally via HART
®
the error is reported binary via the digital output (Digital
Out) if this output has been set to WARNING + ERROR
(see chapter 2.30, page 3-357)
the fault current goes to >21mA
If the error is no longer displayed in Active Error, you can
check the error log (Device Config Diagnostic Log,
page 3-387). In chapter 8 on page 3-429 you find a list of pos-
sible causes and troubleshooting procedures.