Volume 1 8 Visual Inspection
1
8 Visual Inspection
Regular visual inspections of the measuring system SENSseries
have to be carried out, at least once a year. To do this, use the
visual inspection plan on page 1-51. Take appropriate actions
immediately if you detect damage in the course of the visual
inspection; if necessary, disconnect the detector from power supply
immediately.
To determine the inspection intervals for the visual inspection, take
the following conditions into consideration:
– Ambient conditions (outdoor, rain, sunlight, heat and cold).
– Operating conditions (utilization of system, operating errors)
– Measuring system is operated within or outside of an explosion
hazardous zone.
Carry out a visual inspection before first commissioning and after
any repair that requires opening of the detector cover and check the
terminal compartment. Please use the visual inspection plan (Vol-
ume 1) on page 1-51 and the plan for checking the terminal com-
partment on page 1-53.