NOTICE
In automatic reset mode, the motor can start without a warning.
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Manual reset Perform a reset via Stop/Reset button or via the digital inputs.
1 Automatic reset x 1
2 Automatic reset x 2
3 Automatic reset x 3
4 Automatic reset x 4
5 Automatic reset x 5
6 Automatic reset x 6
7 Automatic reset x 7
8 Automatic reset x 8
9 Automatic reset x 9
10 Automatic reset x 10
11 Automatic reset x 15
12 Automatic reset x 20
13 Infinite auto reset Select for continuous resetting after tripping.
14 Reset at power-up
NOTICE
If the specified number of automatic resets is reached within 10 minutes, the frequency converter enters [0] Manual Reset Mode.
After the manual rest is performed, the setting of P 6.6.6 Reset Mode reverts to the original selection. If the number of automatic
resets is not reached within 10 minutes, or when a manual reset is performed, the internal automatic reset counter returns to 0.
P 6.6.7 Automatic Restart Time
Use this parameter to enter the time interval from the trip event to the automatic reset. This parameter is active when P 6.6.6 Reset Mode
is set to a selection between [1]–[13].
Default value: 10 Parameter type: Range (0–600)
Parameter
number:
1421 Unit: s
Data type: uint16 Access type: Read/Write
NOTICE
A value of 0s cannot be set when P 6.6.6 Reset Mode is set to [13] Infinite auto reset.
194 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters