Application Guide | iC2-Micro Frequency Converters
Selection number Selection name Selection description
39 Start command This event is True, if frequency converter is started by any means
(digital input or other).
40 Drive stopped This event is True, if frequency converter is stopped or coasted by
any means (digital input or other).
42 Auto Reset Trip An auto reset is performed.
50 Comparator 4 Use result of comparator 4 in logic rule.
51 Comparator 5 Use result of comparator 5 in logic rule.
60 Logic rule 4 Use result of logic rule 4 in logic rule.
61 Logic rule 5 Use result of logic rule 5 in logic rule.
83 Lost Load Lost load is performed.
P 8.4.2.3 Stop Controller
Select the condition (TRUE or FALSE) to deactivate the Smart Logic Controller.
Default value: 40 Parameter type: Selection
Parameter
number:
1302 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 FALSE Enters False in logic rule.
1 TRUE Enters True in logic rule.
2 Running See P 9.4.3.1 Function Relay [5] for description.
3 In range See P 9.4.3.1 Function Relay [7] for description.
4 On reference See P 9.4.3.1 Function Relay [8] for description.
7 Out of current range See P 9.4.3.1 Function Relay [12] for description.
8 Below I low See P 9.4.3.1 Function Relay [13] for description.
9 Above I high See P 9.4.3.1 Function Relay [14] for description.
16 Thermal warning See P 9.4.3.1 Function Relay [21] for description.
17 Mains out of range Mains voltage is outside the specified voltage range.
18 Reversing See P 9.4.3.1 Function Relay [25] for description.
19 Warning A warning is active.
20 Alarm (trip) A trip alarm is active.
21 Alarm (trip lock) A trip lock alarm is active.