7.7.2 UL Compliance
1x200–240 V, Enclosure Sizes A, B, and C
Recommended maximum fuse
Power
[kW
(hp)]
Max.
prefuse
size [A]
Buss-
mann
JFHR2
Buss-
mann
RK1
Buss-
mann
J
Buss-
mann
T
Buss-
mann
CC
Buss-
mann
CC
Buss-
mann
CC
SIBA
RK1
Littelfu
se
RK1
Ferraz-
Shawmut
CC
Ferraz-
Shawmut
RK1
Ferraz-
Shawmut
J
1.1
(1.5) 15 FWX-15 KTN-R15 JKS-15 JJN-15
FNQ-
R-15
KTK-
R-15
LP-
CC-15
5017906-
016
KLN-
R15 ATM-R15 A2K-15R HSJ15
1.5 (2) 20 FWX-20 KTN-R20 JKS-20 JJN-20
FNQ-
R-20
KTK-
R-20
LP-
CC-20
5017906-
020
KLN-
R20 ATM-R20 A2K-20R HSJ20
2.2 (3) 30
1)
FWX-30 KTN-R30 JKS-30 JJN-30
FNQ-
R-30
KTK-
R-30
LP-
CC-30
5012406-
032
KLN-
R30 ATM-R30 A2K-30R HSJ30
3.0 (4) 35 FWX-35 KTN-R35 JKS-35 JJN-35 --- --- --- ---
KLN-
R35 --- A2K-35R HSJ35
3.7 (5) 50 FWX-50 KTN-R50 JKS-50 JJN-50 --- --- ---
5014006-
050
KLN-
R50 --- A2K-50R HSJ50
5.5
(7.5) 60
2)
FWX-60 KTN-R60 JKS-60 JJN-60 --- --- ---
5014006-
063
KLN-
R60 --- A2K-60R HSJ60
7.5
(10) 80 FWX-80 KTN-R80 JKS-80 JJN-80 --- --- ---
5014006-
080
KLN-
R80 --- A2K-80R HSJ80
15
(20) 150
FWX-
150
KTN-
R150 JKS-150 JJN-150 --- --- ---
2028220-
150
KLN-
R150 --- A2K-150R HSJ150
22
(30) 200
FWX-
200
KTN-
R200 JKS-200 JJN-200 --- --- ---
2028220-
200
KLN-
R200 --- A2K-200R HSJ200
Table 7.23 1x200–240 V, Enclosure Sizes A, B, and C
1) Siba allowed up to 32 A.
2) Siba allowed up to 63 A.
1x380–500 V, Enclosure Sizes B and C
Recommended maximum fuse
Power
[kW
(hp)]
Max.
pre-
fuse
size
[A]
Buss-
mann
JFHR2
Buss-
mann
RK1
Buss-
mann
J
Buss-
mann
T
Buss-
mann
CC
Buss-
mann
CC
Buss-
mann
CC
SIBA
RK1
Littelfus
e
RK1
Ferraz-
Shawmut
CC
Ferraz-
Shawmut
RK1
Ferraz-
Shawmut
J
7.5
(10) 60 FWH-60 KTS-R60 JKS-60 JJS-60
5014006-
063 KLS-R60 - A6K-60R HSJ60
11 (15) 80 FWH-80 KTS-R80 JKS-80 JJS-80
2028220-
100 KLS-R80 - A6K-80R HSJ80
22 (30) 150
FWH-
150
KTS-
R150 JKS-150 JJS-150
2028220-
160 KLS-R150 - A6K-150R HSJ150
37 (50) 200
FWH-
200
KTS-
R200 JKS-200 JJS-200
2028220-
200 KLS-200 A6K-200R HSJ200
Table 7.24 1x380–500 V, Enclosure Sizes B and C
KTS fuses from Bussmann may substitute KTN for 240 V adjustable frequency drives.
FWH fuses from Bussmann may substitute FWX for 240 V adjustable frequency drives.
JJS fuses from Bussmann may substitute JJN for 240 V adjustable frequency drives
KLSR fuses from Littelfuse may substitute KLNR fuses for 240 V adjustable frequency drives.
Specications
Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 175
7 7

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals