Some parameters have different default settings for international or North America. For a list of the different default values, see the
International/North American Default Parameter Settings section.
Parameter settings are stored internally in the drive, allowing the following advantages:
Parameter settings can be uploaded into the LCP memory and stored as a back-up.
Multiple units can be programmed quickly by connecting the LCP to the unit and downloading the stored parameter settings.
Settings that are stored in the LCP are not changed when restoring factory default settings.
Changes made to default settings and parameter variables are stored and available for viewing in the quick menu. See the LCP
Menu section.
7.5.2 Uploading and Downloading Parameter Settings
Context:
The drive operates using parameters stored on the control card, which is located within the drive. The upload and download functions
move the parameters between the control card and the LCP.
Procedure
1. Press [Off].
2. Go to parameter 0-50 LCP Copy and press [OK].
3. Select 1 of the following:
- To upload data from the control card to the LCP, select [1] All to LCP.
- To download data from the LCP to the control card, select [2] All from LCP.
4. Press [OK].
A progress bar shows the uploading or downloading process.
5. Press [Hand On] or [Auto On].
7.5.3 Restoring Factory Default Settings Using the Recommended Initialization
Context:
NOTI C E
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
-
To create a back-up, upload data to the LCP before initialization. See 7.5.2 Uploading and Downloading Parameter Settings.
Commissioning
Operating Guide | VLT® AQUA Drive FC 202
AQ262141056213en-000101 / 130R0882 | 107
Danfoss A/S © 2018.10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals