Table 106: Mains Contactor Fuses for N355–N560 Models, 380–480 V
N355 N400 N450 N500 N560
IEC 580 A/1000 V 580 A/1000 V 580 A/1000 V 820 A/1000 V 820 A/1000 V
Eaton P/N XTCE580N22A XTCE580N22A XTCE580N22A XTCE820N22A XTCE820N22A
UL 820 A/1000 V 820 A/1000 V 820 A/1000 V 1000 A/1000 V 1000 A/1000 V
Eaton P/N XTCE820N22A XTCE820N22A XTCE820N22A XTCEC10N22A XTCEC10N22A
Table 107: Mains Contactor Fuses for N110–N315 Models, 525–690 V
N110 N132 N160 N200 N250 N315
IEC 185 A/1000 V 185 A/1000 V 185 A/1000 V 400 A/1000 V 400 A/1000 V 400 A/1000 V
Eaton P/N XTCE400H22A XTCE400H22A XTCE400H22A XTCE400M22A XTCE400M22A XTCE400M22A
UL 185 A/1000 V 185 A/1000 V 185 A/1000 V 400 A/1000 V 400 A/1000 V 400 A/1000 V
Eaton P/N XTCE400H22A XTCE400H22A XTCE400H22A XTCE400M22A XTCE400M22A XTCE400M22A
Table 108: Mains Contactor Fuses for N400–N630 Models, 525–690 V
N400 N450 N500 N560 N630
IEC 400 A/1000 V 580 A/1000 V 580 A/1000 V 580 A/1000 V 580 A/1000 V
Eaton P/N XTCE400M22A XTCE580N22A XTCE580N22A XTCE580N22A XTCE580N22A
UL 400 A/1000 V 580 A/1000 V 580 A/1000 V 580 A/1000 V 580 A/1000 V
Eaton P/N XTCE400M22A XTCE580N22A XTCE580N22A XTCE580N22A XTCE580N22A
Table 109: Mains Contactor Fuses for N710–N800 Models, 525–690 V
N710 N800
IEC 580 A/1000 V 820 A/1000 V
Eaton P/N XTCE580N22A XTCE820N22A
UL 820 A/1000 V 1000 A/1000 V
Eaton P/N XTCE820N22A XTCEC10N22A
10.8.6 Molded-case Circuit Breakers
The molded-case circuit breaker (MCCB) is an option that combines a temperature sensitive device with a current sensitive
electromagnetic device to protect the drive.
Table 110: MCCB Part Numbers for N110–N315 Models, 380–480 V
N110 N132 N160 N200 N250 N315
IEC 400 A/600 V 400 A/600 V 400 A/600 V 800 A/600 V 800 A/600 V 800 A/600 V
ABB P/N T5L400T T5L400T T5L400T T6L800T T6L800T T6L800T
UL 400 A/690 V 400 A/690 V 400 A/690 V 600 A/690 V 600 A/690 V 800 A/690 V
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ262141056213en-000101 / 130R0882
184 | Danfoss A/S © 2018.10