Page #170 background image
3
See also Input Power Option Losses.
4
If using an output filter, the output frequency is limited further. See the Motor Output (U, V, W) section.
10.2 Mains Supply
The unit is suitable for use on a circuit capable of delivering not more than 100 kA short circuit current rating (SCCR) at 480/600 V.
Supply terminals L1, L2, L3
Supply voltage
(1)
380–480/500 V ±10%, 525–690 V ±10%
Supply frequency 50/60 Hz ±5%
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
(2)
True power factor (λ) ≥0.9 nominal at rated load
Displacement power factor (cos Φ) Near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups) Maximum 1 time/2 minutes
Environment according to EN60664-1 Overvoltage category III/pollution degree 2
1
Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop level, which
corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the drive's lowest
rated supply voltage.
2
Calculations based on UL/IEC61800-3.
10.3 Motor Output and Motor Data
10.3.1 Motor Output (U, V, W)
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency (without sine-wave filter)
0–590 Hz
(1)
Output frequency (with sine-wave filter and no derating) 0–60 Hz without derating
Output frequency (with sine-wave filter and derating) 0–100 Hz
Output frequency in flux mode 0–300 Hz
Switching on output Unlimited
Ramp times 0.01–3600 s
1
Dependent on voltage and power.
10.3.2 Torque Characteristics
Torque characteristics
Starting torque (constant torque)
Maximum 160% for 60 s once in 10 minutes
(1)
Starting/overload torque (variable torque)
Maximum 110% up to 0.5 s once in 10 minutes
(1)
Torque rise time in flux (for 5 kHz f
sw
) 1 ms
Torque rise time in VVC
+
(independent of f
sw
)
10 ms
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ262141056213en-000101 / 130R0882
170 | Danfoss A/S © 2018.10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals