Model 525–550 V 551–690 V
N500 64 50 59 45
N560 72 64 72 59
N630 83 62 76 57
N710 76 56 69 51
11.6.2 Fusible Disconnect Losses
Table 124: Power Losses for Fusible Disconnect Option, 380–500 V (Losses Shown in Watts)
Model 380–440 V 441–500 V
– NO HO NO HO
N90K 71 49 57 40
N110 89 59 76 48
N132 131 90 121 76
N160 142 91 119 83
N200 155 105 132 88
N250 233 155 193 132
N315 188 156 151 127
N355 202 158 168 127
N400 233 176 194 168
N450 282 233 222 194
N500 305 241 246 189
Table 125: Power Losses for Fusible Disconnect Option, 525–690 V (Losses Shown in Watts)
Model 525–550 V 551–690 V
– NO HO NO HO
N90K 29 20 27 18
N110 41 29 37 27
N132 63 41 57 37
N160 71 45 65 41
N200 101 70 92 64
N250 118 84 108 77
N315 151 112 138 102
N355 191 135 175 125
N400 134 90 123 83
N500 154 119 141 109