EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 User Manual

Danfoss VLT AQUA Drive FC 202
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
1. Press [Main Menu] twice to access parameters.
2. Go to parameter 14-22 Operation Mode and press [OK].
Parameter 14-22 Operation Mode does not reset the following settings:
Running hours.
Serial communication options.
Personal menu settings.
Fault log, alarm log, and other monitoring functions.
3. Scroll to Initialization and press [OK].
4. Remove power to the unit and wait for the display to turn off.
5. Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal.
6. After alarm 80, Drive initialized appears, press [Reset].
7.5.4 Restoring Factory Default Settings Using Manual Initialization
Context:
NOTI C E
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
-
To create a back-up, upload data to the LCP before initialization. See 7.5.2 Uploading and Downloading Parameter Settings.
Procedure
1. Remove power to the unit and wait for the display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until an
audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
Parameter 15-00 Operating Hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Start-up takes slightly longer than normal.
Commissioning
Operating Guide | VLT® AQUA Drive FC 202
AQ262141056213en-000101 / 130R0882
108 | Danfoss A/S © 2018.10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals