10 Specifications
10.1 Electrical Data
10.1.1 Electrical Data, 380–480 V AC
Table 78: Electrical Data, Mains Supply 3x380–480 V AC
FC 202 N110 N132 N160
High/normal overload
High overload=150% or 160% torque for a duration of 60 s. Normal
overload=110% torque for a duration of 60 s.
HO NO HO NO HO NO
Typical shaft output at 400 V [kW] 90 110 110 132 132 160
Typical shaft output at 460 V [hp] 125 150 150 200 200 250
Typical shaft output at 480 V [kW] 110 132 132 160 160 200
Enclosure size D9h D9h D9h
Output current (3-phase)
Continuous (at 400 V) [A] 177 212 212 260 260 315
Intermittent (60 s overload) (at 400 V) [A] 266 233 318 286 390 347
Continuous (at 460/480 V) [A] 160 190 190 240 240 302
Intermittent (60 s overload) (at 460/480 V) [A] 240 209 285 264 360 332
Continuous kVA (at 400 V) [kVA] 123 147 147 180 180 218
Continuous kVA (at 460 V) [kVA] 127 151 151 191 191 241
Continuous kVA (at 480 V) [kVA] 139 165 165 208 208 262
Maximum input current
Continuous (at 400 V) [A] 171 204 204 251 251 304
Continuous (at 460/480 V) [A] 154 183 183 231 231 291
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm)
- Mains with disconnect [mm
2
(AWG)]
2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm)
- Mains with contactor [mm
2
(AWG)]
2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm)
- Motor [mm
2
(AWG)]
2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm)
Drive module power loss at 400 V [W]
(1) (2) (3)
2031 2559 2289 2954 2923 3770
Drive module power loss at 460 V [W]
(1) (2) (3)
1828 2261 2051 2724 2089 3628
Drive efficiency
(2)
0.98 0.98 0.98
Output frequency [Hz]
(4)
0–590 0–590 0–590
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ262141056213en-000101 / 130R0882