Model 525–550 V 551–690 V
N560 173 154 173 141
N630 208 155 190 142
N710 282 208 258 190
11.6.3 Non-fusible Disconnect Losses
Table 126: Power Losses for Non-fusible Disconnect Option, 380–500 V (Losses Shown in Watts)
Model 380–440 V 441–500 V
NO HO NO HO
N90K 8 6 7 5
N110 13 8 11 7
N132 19 13 17 11
N160 29 19 25 17
N200 44 29 37 25
N250 65 44 54 37
N315 25 21 20 17
N355 32 25 26 20
N400 36 27 30 26
N450 43 36 34 30
N500 55 43 44 34
Table 127: Power Losses for Non-fusible Disconnect Option, 525–690 V (Losses Shown in Watts)
Model 525–550 V 551–690 V
NO HO NO HO
N90K 4 2 3 2
N110 5 4 5 3
N132 8 5 7 5
N160 12 8 11 7
N200 17 12 16 11
N250 24 17 22 16
N315 33 24 30 22
N355 42 29 38 27
N400 52 35 47 32
N500 20 16 19 14
N560 23 20 23 19