Troubleshooting
• To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the
cards.
9.3.69 ALARM 71, PTC 1 Safe Stop
Cause
Because the motor is too warm, the VLT
®
PTC Thermistor Card MCB 112 activated the Safe Torque Off (STO).
Troubleshooting
• Once the motor temperature reaches an acceptable level and the digital input from MCB 112 is deactivated,send a reset signal via
bus or digital I/O, or press [Reset].
9.3.70 ALARM 72, Dangerous Failure
Cause
Safe Torque Off (STO) with trip lock.
Troubleshooting
An unexpected combination of STO commands has occurred:
• VLT
®
PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled.
• MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 12 warning in parameter 5-19 Terminal
37 Safe Stop). STO is activated, but X44/10 is not activated.
9.3.71 WARNING 73, Safe Stop Auto Restart
Cause
STO activated.
Troubleshooting
• With automatic restart enabled, the motor can start when the fault is cleared.
9.3.72 ALARM 74, PTC Thermistor
Cause
The PTC is not working. Alarm is related to VLT
®
PTC Thermistor Card MCB 112.
9.3.73 ALARM 75, Illegal Profile Sel.
Cause
Do not write the parameter value while the motor is running.